Laboratory Test Request

Materials Testing on Bricks and Mortar

Project Description

URGENT TESTING
We have been tasked with repairing an old building in Shelbyville TN the engineer has requested that we have testing on the bricks of the building done.

Test each type of existing masonry unit indicated on drawings according
to testing methods in ASTM C 67 for compressive strength, 24-hour cold-water
absorption, five-hour boil absorption, saturation coefficient, and initial rate of
absorption (suction). Carefully remove two (2) existing units from locations designated
on drawings. Take testing samples from these units.
3. Existing Mortar: Test according to ASTM C 270, modified as agreed by testing service
and Architect for Project requirements, to determine proportional composition of
original ingredients, sizes and colors of aggregates, and approximate compressive
strength.
4. Existing Grout (if presented in existing wall): Test according to ASTM C1019, Standard
Test Method for Sampling and Testing Grout, to determine proportional composition of
original ingredients and compressive strength.

Project Information

Number:24-00562

Industry:Bricks, Pavers, and Masonry

This request is closed and is no longer accepting quotes. Register or Log In to receive alerts when similar requests open in the future.
Bricks, Pavers, and Masonry,

Test Request: 25-00545

An engineering & construction management company needs Solar Reflectance Index (SRI) testing for a pavement type ... view


Test Request: 25-00236

We are doing asphalting inside our company (~6300m2 area). We need to test the ongoing soil compaction. view


Test Request: 25-00188

MULTIPLE TESTING

We need the following tests on concrete blocks and we will send them to you:

1. Absorpti... view